UT276A+ can quickly and safely measure the grounding system without disconnecting circuit ground lines or the need of auxiliary electrodes. It can measure resistance from 0.01Ω with a resolution of 0.001Ω. This clamp’s double insulation design makes it a durable tool for outdoor work and effective in blocking interference signals from the environment.
FEATURES:
- Auto range
- Data hold
- Data recall
- LCD backlight
- Resistance limit alarm
- Low battery indication
- Auto calibration.
INCLUDES:
1 x UT276A+, Batteries, test ring, 1 x English manual and 12-month warranty.
SPECIFICATIONS:
| Specifications | Range | UT276A+ | UT278A+ |
| Earth Ground Resistance (Ω) | 0.01~0.099Ω | ±(1%+0.01) | ±(1%+0.01) |
| 0.1~0.99Ω | ±(1%+0.01) | ±(1%+0.01) | |
| 1~49.9Ω | ±(1%+0.1) | ±(1%+0.1) | |
| 50~99.5Ω | ±(1.5%+0.5) | ±(1.5%+0.5) | |
| 100~199Ω | ±(2%+1) | ±(2%+1) | |
| 200~395Ω | ±(5%+5) | ±(5%+5) | |
| 400~590Ω | ±(10%+10) | ±(10%+10) | |
| 600~800Ω | ±(20%+20) | ||
| 600~1000Ω | |||
| 800~1200Ω | ±(25%+30) | ||
| Leakage current (A) | 0mA~9mA | ±(2.5%+1mA) | |
| 10mA~99mA | ±(2.5%+5mA) | ||
| 100mA~299mA | ±(2.5%+10mA) | ||
| 0mA~299mA | |||
| 0.3A~2.99A | ±(2.5%+0.1A) | ||
| 3A~9.9A | ±(2.5%+0.3A) | ||
| 10A~20A | ±(2.5%+0.5A) | ||
| 3A~30A | |||
| Display count | 4 digits LCDÂ display | ||
| Jaw opening | 32mm | 32mm | |
| Visual and audible alarm | √ | √ | |
| Auto power off | √ | √ | |
| Jamming signal recognition | √ | √ | |
| Over-range display | √ | √ | |
| Data storage | 300 | 300 | |
| Display type | EBTN | EBTN | |
| Ω+A display | √ | ||
| General Characteristics | |||
| Power | 1.5V battery (LR6) x 4 | ||
| Display | 47mm x 28.5mm | ||
| Product net weight | UT273/275: 1.32kg; UT276A+/278A+: 1.18kg | ||
| Product size | UT273/275: 293mm x 90mm x 66mm; UT276A+/278A+: 285mm x 85mm x 56mm | ||
| Standard accessories | Batteries, test ring, English manual | ||
| Standard individual packing | Box, toolbox | ||