INFICON Pilot Plus Vacuum Gauge incorporates several innovative features for unsurpassed performance. Like the Pilot, it’s the only gauge to use a Pirani sensor for greater accuracy and the ability to measure the entire vacuum process, from atmosphere down to one micron. You’ll know instantly if your connections are vacuum-tight. And Pilot Plus is even more unique: An industry-first filter protects the sensor from oil and other contaminants for more accurate readings and saves you from having to clean the vacuum sensor. Quick calibration allows you to adjust Pilot Plus for slight variations in atmospheric pressure at your specific geographic location to ensure greater accuracy. You also get an extended battery life of up to 45 hours from one 9-volt battery, to keep you productive on the job. That’s three times longer than before. To maximize that battery life, Pilot Plus shuts down after 60 minutes and saves the last reading for display again upon the next start-up. User-friendly qualities of a large, easy-to-read LCD and included plastic storage case complete the Pilot Plus package.
FEATURES:
- Operates for 45 hours on one 9V battery
- Quick calibration specific to local pressure
- Displays in micron, Pascal, Torr or millibar
- Low battery indicator
- Plastic storage case included
- 1-year replacement warranty
- Made in the USA.
ADVANTAGES:
- Innovative filter protects sensor, eliminates need for cleaning
- Measures from atmosphere to 1 micron
- Auto shut-off after 60 minutes to conserve battery
- Only vacuum gauge using a Pirani sensor for better accuracy
- Large, easy-to-read LCD display.
APPLICATIONS:
- Vacuum measurement in HVAC/R service
INCLUDES:
1 x 710-202-G27 Vacuum gauge, 1 x Hard carrying case, 1 x English manual and 12 month warranty
SPECIFICATIONS:
Type | Pilot Plus | |
---|---|---|
Base unit includes | 9V battery, filters, storage case | |
Battery life | 45 hours | |
Power source | (1) 9V alkaline battery, included | |
Controls | On/off, unit selection, quick calibration | |
Display units | microns, Pascal, millibar, Torr | |
Display range | atm (760,000 microns) to 1 micron (0.01 mbar, 0.001 Torr, 1 Pa) | |
Auto shut-off | After 60 minutes; last reading displayed when restarted | |
Connection | KF-16 Fitting |
|
Maximum overpressure | 150 psi (7.76 x 106 microns) (10 bar) |